Commercial kitchen
Case Study

Walk-In Cooler Compressor Failure
— Downtown Montreal

Downtown Montreal 3h 20min from call to resolution

A downtown Montreal restaurant discovered their True T-72 walk-in cooler had stopped cooling overnight. Interior temperature had reached 58°F. Flash Repair was called at 7:30 AM and had the unit repaired and cooling by 10:50 AM — before the lunch service.

The restaurant manager arrived at 7:00 AM to begin prep work and immediately noticed the walk-in cooler was warm. The unit was still running — the compressor was attempting to start — but producing no cooling effect. Interior temperature was 58°F (14°C), well above the safe threshold for food storage.

With a full lunch and dinner service scheduled, the restaurant faced a critical decision: move the food immediately and call for emergency service, or risk the health code violation. They called Flash Repair at 7:30 AM.

7:30 AM

Call received. Manager describes clicking sound from condensing unit, warm interior.

7:45 AM

Flash Repair technician dispatched from Montreal base.

8:15 AM

Technician arrives. Immediate diagnosis: Bristol compressor hard start failure. Start capacitor blown, compressor locked rotor.

8:30 AM

Start relay and capacitor confirmed failed. Compressor checked — windings intact, motor viable with hard start kit.

9:00 AM

Hard start kit installed, start components replaced. Compressor test — successful start, amperage normal.

9:30 AM

Refrigerant pressures checked — within spec. System running, temperatures dropping.

10:50 AM

Interior temperature reached 36°F. System stable. Food safety restored before lunch service.

Primary: Start Capacitor Failure

The start capacitor provides the initial voltage kick to start the compressor motor. Once it fails, the compressor clicks but cannot start, leading to a locked rotor condition.

Secondary: Start Relay Worn

The start relay, which works alongside the capacitor, was at end of life and replaced simultaneously to prevent recurrence.

Bristol compressor start capacitor (replacement, OEM-equivalent)

Compressor start relay (replacement)

Hard start kit installed for reduced startup amperage

Full refrigerant pressure check — no recharge needed

Condensing unit area cleaned (minor dust on coils)

3h 20m

Call to Resolution

$0

Food Loss (service before lunch)

36°F

Target Temp Achieved

Same Issue?

Walk-in not cooling? Call now — we can often diagnose over the phone.

438-700-9164Book Service

Equipment

True T-72 Walk-In Cooler

Location

Downtown Montreal

Response Time

45 minutes

Repair Time

2 hours 35 minutes

Repair Cost

$380 (parts + labour)